Multi-function Safety Modules: MFU-M1: Single Light Curtain with Mute Module

 Please choose from the following topics 

          MFU-M1: Specifications & Dimension

          MFU-M1: Controls Information

 

MFU-M1 Specifications 
Response Time 25 ms Max.
Operating Temperature 0° to +50°C
Enclosure Rating IP40 
Enclosure 70 mm DIN rail mounting (HxWxD) 90x70x60
Power Supply 24V DC ± 10% reg.
Current Consumption 150mA (NO LOAD)
Status Indicators LED's: for all inputs & outputs
INPUTS

Dual Safety Inputs light curtain 

 

24V DC = ON, 0V = OFF; Disparity between related channels = 500ms max.
Dual Inputs for mute sensors 24V DC = ON , 0V = OFF; Disparity between channels = 10 sec max.
Dual Inputs for emergency-stop circuit Use voltage free switch contacts; Disparity between channels = 100ms
External Device Monitoring (EDM) Use voltage free contacts 
Reset Function (selectable) 24V DC = ON , 0V = OFF
OUTPUTS
Safety Outputs 2 x N.O.  fail safe change over contacts, each rated at 250V AC @ 2A
Auxiliary solid-state switch (Non-Safety)

1 x  electronic output switch , rated at 

24V DC @ 500mA

Auxiliary solid-state switch for mute indication

1 x  electronic output switch , rated at 

24V DC @ 500mA

Return to MFU-M1:Index


MFU-M1: Controls Information

To enlarge the diagram click on the controls diagram below.

 

011151.jpg (29529 bytes)

Status Indicators

Inputs - Green LED ON when input is ON

Outputs - Green LED ON when input is ON

Reset - Yellow LED ON when reset input is ON

EDM - Yellow LED ON when EDM inputs are ACTIVE

Status - RED LED's ON steady when the system is OK

              RED LED's flash ON/OFF when the system is in lockout

Wiring Information

Terminals A1 and A2 – Power supply input - Connect a suitably stabilized 24V DC power supply to terminals A1 = +24V DC and A2 = 0V DC.  The current consumption of the MFU with no load applied on the output switching terminals is 150mA.

 

Terminals A3 and A4 – External device monitor (EDM) - Normally closed switch contacts, in series from the external power switching devices are connected across terminals A3 and A4.  The monitoring circuit checks that the power switching devices both de-energize at the same time the MFU safety output switches de-energize.  If one or both of the power switching devices fail to de-energize at this time the MFU goes into a lockout condition, turning all output switches off.

To reset from a lockout condition it is necessary to remove the 24V DC supply from the MFU and then re-apply.

If the EDM circuit is not used it is necessary to link terminals A3 to A4 otherwise the system will go to a lockout condition at the next demand upon the safety system.

Terminals A5 and A6 – Safety output 1 switch contact - Connect terminals A5 and A6 to one channel of a machine’s stop circuitry.  For example, via an external power-switching relay or directly to a safe PLC input or a machines final control element.

 

Terminals A7 and A8 – Safety output 2 switch contact - Connect terminals A7 and A8 to one channel of a machine’s stop circuitry.  For example, via an external power-switching relay or directly to a safe PLC input or a machines final control element.

If a single channel safety circuit is used link terminals A6 and A7.  Terminals A5 and A8 are then connected to the machine’s safety circuit.  Connecting in this way links safety output switch 1 and safety output switch 2 in a series configuration.

Terminal A9 – No connection

Terminal A10 – Auxiliary electronic switching output 1 - The Auxiliary switching output should only be used for non-safety critical application.  For example connecting an indicator lamp or as feedback to a PLC to confirm the safety outputs have de-energies.

The auxiliary output energizes when safety output switches 1 and 2 energize and de-energizes when the safety outputs de-energize.  Auxiliary output ON = 24V DC and OFF = 0V DC.

Terminal A11 – Auxiliary electronic switch – mute out.- The Auxiliary switching circuit energizes when the light curtain is muted, e.g. when suitable signals have been applied to terminals B2 and B3.  The output switch is normally used for connecting an indicator lamp or as feedback to a PLC to confirm safety light curtain inputs at terminals B1 and B2 are overridden e.g. in a muted condition.

Terminal A12 – Reset - A suitable switch should be connected between terminal A12 and the 24V DC supply.  If the safety output relays de-energize a depression of the switch is required to re-energize the output switches to an ON condition.

The MFU’s safety output switches will only re-energize when the reset switch is depressed and then released.

Terminal B1 and B2 – light curtain inputs (OSSD1 and OSSD2) - Connect the electronic output switches (OSSD1 and OSSD2) of a light curtain to terminals B1 and B2 respectively.

Note: An internal circuit monitors disparity between the two input channels.  If the inputs do not switch together (within 500ms of each other) the system will go into a lockout condition.

Important: If terminal B1/B2 are not used it is necessary to link them to the 24V DC supply.  If not the MFU’s output switches will not energize.

Terminal B3 and B4 – mute input signals - Connect suitable mute initiating signals to terminals B3 and B4 respectively.  The mute signals override the light curtains operation therefore, the inputs should only be active during safe periods of the machinery’s operating cycle.

Note: An internal circuit monitors disparity between the two mute input channels.  If the inputs do not switch within 10 secs. of each other the system will go into a lockout condition

Terminals B5/B6 and B7/B8 – dual channel emergency stop circuit - Connect one channel of the machines emergency stop circuit between terminals B5 and B6 and the second channel between terminals B7 and B8.

Note: An internal circuit monitors for short circuits and switching disparity between the two input channels.  If the inputs do not switch together (within 100ms of each other) the system will go into a lockout condition.  This configuration meets the requirements for ‘control reliability’ and cannot be used in a single channel configuration.

Important, if the emergency stop inputs are not used; it is necessary to link terminals B5 to B6 and terminals B7 to B8.  If not the safety output switches will not energize.

Terminals B9 and B11 – 24V DC supply - Additional + 24V DC outputs for connecting to the light curtains etc.

Terminals B10 and B12 – 0V DC supply - Additional 0V DC outputs for connecting to the light curtains etc.

Return to MFU-M1:Index

 

                                            

Master Card Logo.jpg (66282 bytes)Visa Logo.jpg (78649 bytes)

Products    Distributors    Applications    Sizing   Contact US 

If you have any problems or comments concerning this website

contact: webmaster@smartscaninc.com

The information and drawings contained herein are the sole property of Smartscan Incorporated.  The information on this website is subject to change without notice. Smartscan Incorporated shall not be liable for any errors contained herein for incidental or consequential damages in connection with the performance or use of this material.